Thien Son Technology Corporation
Hotline: 1900 6697
Hotline: 1900 6697

Voltage measuring transducers – MCR-VAC-UI-O-DC – 2811103

*Description: MCR voltage measuring transducer, for alternating current voltages from 0..20 V AC to 0..440 V AC, output signal 0..10 V/0(4)..20 mA

*Country of origin: DE (Germany)

 Logo

Your advantages

-Replacement device MACX MCR-VAC-(PT) 2906239 with 8 measurement ranges from 0 V … 20 V AC to 0 V … 660 V AC, output signals: 0 V … 10 V / 0 (4) mA … 20 mA

-Adjustable voltage ranges

-Bidirectional output signals

– 3-way isolation

-ZERO/SPAN adjustment ±20%

-Tool-free parameterization of measured values

-Teach-in configuration of the measured value range

 

 

Mua ngay Gọi điện xác nhận và giao hàng tận nơi

Dimensions

Width 22.5 mm
Height 99 mm
Depth 114.5 mm

Ambient conditions

Ambient temperature (operation) -25 °C … 60 °C
Ambient temperature (storage/transport) -40 °C … 85 °C (non-condensing)
Maximum altitude < 2000 m
Degree of protection IP20
Noise immunity EN 61000-6-2

Input data

Input voltage range 0 V … 370 V AC
Input resistance 370 kΩ
Input voltage range 0 V … 250 V AC
Input resistance 250 kΩ
Input voltage range 0 V … 170 V AC
Input resistance 170 kΩ
Input voltage range 0 V … 120 V AC
Input resistance 120 kΩ
Input voltage range 0 V … 80 V AC
Input resistance 80 kΩ
Input voltage range 0 V … 54 V AC
Input resistance 54 kΩ
Input voltage range 0 V … 36 V AC
Input resistance 36 kΩ
Input voltage range 0 V … 24 V AC
Input resistance 24 kΩ
Nom. voltage 440 V (ungrounded)
250 V (to earth)

Output data

Output name Voltage output
Voltage output signal 0 V … 10 V
Max. output voltage 15 V
Load/output load voltage output > 10 kΩ
Ripple < 50 mVPP
Output name Current output
Current output signal 0 mA … 20 mA
4 mA … 20 mA
Max. output current 30 mA
Load/output load current output < 500 Ω
Ripple < 50 mVPP

Power supply

Supply voltage range 18.5 V DC … 30.2 V DC
Max. current consumption < 45 mA

 